DSCA45-06E

Frequency Input Signal Conditioner

DSCA45-06E
Frequency Input Signal Conditioner

Product Availability:
  • Usually stock to 2-3 weeks.

Description

Each DSCA45 frequency input module provides a single channel of frequency input which is isolated and converted to a standard analog voltage or current output.

The frequency input signal can be a TTL level or zero-crossing signal. Terminal 7 (-IN) on the field-side terminal block is the "common" or ground connection for input signals. A TTL signal is connected from terminal 6 (+IN) to terminal 7 (-IN), while a zero-crossing signal is connected from terminal 5 (+EXC) to terminal 7 (-IN). Input circuitry for each of the signal types has hysteresis built in. An input signal must cross entirely through the hysteresis region in order to trigger the threshold comparator.

A +5.1V excitation is available for use with magnetic pick-up or contact-closure type sensors. The excitation is available on terminal 8 (-EXC) with return at terminal 7 (-IN).

Module output is either voltage or current. For current output models a dedicated loop supply is provided at terminal 3 (+OUT) with loop return located at terminal 4 (-OUT). The system-side load may be either floating or grounded.

Special input circuits provide protection against accidental connection of powerline voltages up to 480VAC and against transient events as defined by ANSI/ IEEE C37.90.1. Protection circuits are also present on the signal output and power input terminals to guard against transient events and power reversal. Signal and power lines are secured to the module using screw terminals which are pluggable terminal blocks for ease of system assembly and reconfiguration.

DSCA45 modules have excellent stability over time and do not require recalibration, however, both zero and span settings are adjustable to accommodate situations where fine tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.

Specifications

  • Input Range 0 to 25 kHz
  • Output Range 0 to 20 mA
  • Zero Crossing Hysterisis 40mV
  • Mechanical Format DIN rail
  • Isolation Voltage 1500 Vrms
  • Isolation Type Transformer 3-way
  • Accuracy ±0.05% Span
  • Supply Voltage 19 to 29 Vdc (+24V Nom)
  • Input Voltage Withstand 240 Vrms
  • Gain/Offset Adjust ±5%
  • External I-to-V Resistor N/A
  • Output Control Always enabled
  • Output Resistance <1 Ohm
  • Dimensions 2.95 x 0.89 x 4.13 inches
  • Interface 8 Pos terminal block
  • Customization yes
  • Weight 99 grams (3.49 ounces)

Features

  • Accepts Frequency Inputs of 0 to 100kHz
  • Industry Standard Output of Either 0-10V, 0-20mA, or 4-20mA
  • ±0.05% Factory Calibrated Accuracy
  • Adjustable Zero (±5%) and Span (±5%)
  • 1500Vrms Transformer Isolation
  • Input Overload Protected to 240VAC Continuous
  • ANSI/IEEE C37.90.1 Transient Protection
  • Mounts on Standard DIN Rail
  • C-UL-US Listed
  • CE and ATEX Compliant

Block Diagram

DSCA45 block diagram

Accessories

DSCAX-01
Connector Plug Labeled 1,2,3,4 View
DSCAX-02
Connector Plug Labeled 5,6,7,8 View
DSCX-BLANK
Blank Empty DIN Rail Case for Holding Positiion. DSCA or DSCT View
PWR-PS5R120W
Power Supply, DIN Rail Mount, 85-264 VAC 47-63 Hz In, 24 VDC 5.0 A Out View
PWR-PS5R15W
Power Supply, DIN Rail Mount, 85-264 VAC 47-63 Hz In, 24 VDC 0.65 A Out View
PWR-PS5R30W
Power Supply, DIN Rail Mount, 85-264 VAC 47-63 Hz In, 24 VDC 1.3 A Out View
PWR-PS5R60W
Power Supply, DIN Rail Mount, 85-264 VAC 47-63 Hz In, 24 VDC 2.5 A Out View
PWR-PS5R7W
Power Supply, DIN Rail Mount, 85-264 VAC 47-63 Hz In, 24 VDC 0.3 A Out View
SCMXRAIL1-1.0
DIN EN 50022-35 x 7.5 (slotted steel), 1 meter length View
SCMXRAIL1-2.0
DIN EN 50022-35 x 7.5 (slotted steel), 2 meter length View
SCMXRAIL2-01
DIN EN 50035-G32 (slotted steel), 1 meter length View
SCMXRAIL2-02
DIN EN 50035-G32 (slotted steel), 2 meter length View
SCMXRAIL3-01
DIN EN 50022-35 x 15 (slotted steel), 1 meter length View
SCMXRAIL3-02
DIN EN 50022-35 x 15 (slotted steel), 2 meter length View

Competitive Cross-Reference

  • No cross reference is available.
View Dataforth cross-reference data.
The information available through this competitive cross reference guide are based upon product catalog information obtained from a variety of sources. The competitive cross reference information is being provided to you free of charge for your use. While Dataforth Corp has used reasonable efforts to ensure data accuracy, Dataforth Corp does not guarantee that it is error-free, nor does Dataforth Corp make any other representation, warranty or guarantee that the information is accurate, correct, reliable or up-to-date. Dataforth Corp expressly disclaims all implied warranties regarding this information, including but not limited to any implied warranties of merchantability or fitness for a particular purpose.

This information is provided only as a convenience on an "as is" basis and Dataforth Corp. or its representatives or distributors are not responsible for any incorrect, inaccurate, or incomplete information. You are solely responsible for (1) selecting the appropriate Dataforth products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable standards, and any other safety, security, or other requirements.

FAQ

Can Dataforth analog modules be used in high vibration environments? If so, what type of testing or certification was completed?
SCM5B, SCM7B, 8B SensorLex, and DSCA modules are well suited for use in high vibration environments. These modules and their associated accessories have undergone testing for random vibration, shock, and swept sine wave vibration. Details of each of these testing methods are provided below: Random Vibration (Operating): ○ MIL-STD 202G, Method 214A, Condition 1 - Frequency Range: 50-2000Hz, flat spectrum - Vibration Intensity: 7.56 Grms - Duration: 10min/axis (X, Y, Z) Shock (Operating): ○ MIL-STD-810F, Method 516.5 - Pulse Shape: Sawtooth - Test Level: 30G - Duration 11ms - Orientation: +/-X, +/-Y, +/-Z Swept Sine Vibration (Operating) ○ MIL-STD-810G, Method 514.6, modified - Frequency Range: 10-2000Hz - Vibration Intensity: 5Gp-p - Sweep Rate: 1 octave/min - Orientation: X, Y, Z Declaration of conformity for the above-listed tests can be provided upon customer request. Please contact customer service if a copy of the declaration is needed.
Due to resource constraints on my computer, I'm unable to open the three dimensional CAD models provided on your website. Does Dataforth provide two demensional CAD models for download as well?
Two dimensional CAD models can be generated upon customer request. Please contact Customer Service for assistance.
What does it mean when an input module has for example a 3kHz bandwidth?
A 3kHz bandwidth on an input module means it can accept voltages from DC to 3000Hz. Any frequency higher than that and the signal will start to be attenuated by the filter at the input.
What does "Response time, 90% span" mean on the datasheet for my module?
Normally, a response time figure refers to how quickly a module's output can "respond" to a change in the input signal. "Response time, 90% span" refers to how fast a module can adjust its output when a step signal is applied at the input, where the magnitude of this step input is 90% of the input span of the module.
Do DSCA modules come with screw terminal blocks installed?
Yes, DSCA modules do come with the screw terminal blocks installed. The screw terminal accessories listed in our catalog are intended as replacements in case a terminal block is damaged or lost.
What size wires do the DSCA modules accept?
DSCA module screw terminals are rated to wire gage AWG: 28 – 12.
Where can I find the MTBF of my module?
Information on MTBF for SCM5B, SCM7B, 8B and DSCA is available on our website. Please see application note AN802 for more details. Application notes can be found under the "Literature" tab on the top navigation bar.
Does the input of the DSCA45 have a high impedance differential amplifier at the input?
Both the TTL and Zero Crossing inputs are single-ended. Both inputs have a 100kOhm input impedance in the power off condition. The TTL input has an input attenuator, so input resistance is approx. 100kOhm. For Zero Crossing input, signals under +/-0.4V don’t clamp the diode so the 100kOhm is in series with the amplifier input which provides high impedance.
Is the calibration of Dataforth modules traceable to NIST standards?
Yes, calibration of Dataforth modules is traceable to NIST standards.
What is the output resolution of the DSCA series?
The DSCA series is completely analog, so the output resolution cannot be expressed in terms of bits as it is not a digital signal. The only thing that would cause any uncertainty/lack of clarity in your output signal would be the output ripple and noise, which is rated at a typical value of 0.025% span RMS as listed in the datasheet.
How do I wire up a pulse train to the input of my DSCA45 module?
The DSCA45 accepts TTL signal input across input terminals 6 and 7 (+IN and -IN). A pulse train should be wired across terminals 6 and 7 for proper operation.
Does Dataforth have any DSCA modules that can operate on a 12Vdc power supply?
Dataforth does not have any custom modules that run on 12VDC power. Most DSCA modules require a minimum power supply voltage of 15VDC while some require a minimum of 19VDC. Both are suitable for use with nominal 24VDC power supplies over the full operating temperature range of -40C to +85C. Dataforth offers a line of accessory power supplies, PWR-PS5RxW, which have been qualified for use with the DSCA product line. https://www.dataforth.com/catalog/pdf/PWR-PS5RxW.pdf
How does the load resistance of a module affect the noise at the output?
Noise at the output of a module is independent of load resistance.
How do I convert an RMS voltage to its corresponding peak voltage?
To convert an RMS voltage to its corresponding peak voltage, you simply take the RMS voltage value and multiply it by the square root of 2, or roughly 1.414. For example, 1500Vrms corresponds to a peak voltage of 1500 * 1.414 = 2121 Vp
If the input range of my signal conditioner is -1V to +1V and the output range is 0 to 10V, does this mean that it ignores polarity?
A signal conditioner with these I/O ranges does not mean that the module ignores the polarity of your voltage input. The output of voltage input modules are scaled linearly, meaning an input of -1V would correspond to an output of 0V, an input of 0V would correspond to an output of 5V, an input of +1V would correspond to an output of 10V, and so on.
Can Dataforth provide calibration reports for modules I purchased?
Yes we can provide calibration reports for the modules that you purchased. You can either a) visit https://www.dataforth.com/TestDataReport.aspx to search for Test Report Datasheets by Serial Number or b) you can send us a list of model numbers and their serial numbers to support@dataforth.com

Was this content helpful?
Thank you for your feedback!