Each DSCA43 general purpose input module provides a single channel of transducer input which is filtered, isolated, amplified, and converted to a high-level voltage output. Signal filtering is accomplished with a five-pole filter which is optimized for step response. An anti-aliasing pole is located on the field side of the isolation barrier, and the other four poles are on the system side. After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges.

Transducer excitation is provided from the module by a stable 10V source. This source is fully isolated, allowing the amplifier inputs to operate over the full range of the excitation voltage. This feature enables the module to be interfaced to a wide variety of sensors requiring exctitation.

Module output is either voltage or current. For current output models a dedicated loop supply is provided at terminal 3 (+OUT) with loop return located at terminal 4 (-OUT). The system-side load may be either floating or grounded.

Special input circuits provide signal input and excitation protection against accidental connection of power-line voltages up to 240VAC and against transient events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present on the signal output and power input terminals to guard against transient events and power reversal. Signal and power lines are secured to the module using screw terminals which are in pluggable terminal blocks for ease of system assembly and reconfiguration.

The modules have excellent stability over time and do not require recalibration, however, zero and span settings are adjustable up to ±5% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.
  • Interfaces to Transducers and Other Devices Requiring a Stable, Isolated DC Supply
  • Industry Standard Output of Either 0-10V, ±10V, 0-20mA, or 4-20mA
  • 1500Vrms Transformer Isolation
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240VAC Continuous
  • True 3-Way Isolation
  • Wide Range of Supply Voltage
  • 100dB CMR
  • Fully Isolated Excitation Supply
  • ±0.03% Accuracy
  • ±0.01% Linearity
  • Easily Mounts on Standard DIN Rail
  • C-UL-US Listed
  • CE and ATEX Compliant
General Purpose Input Signal Conditioners, with DC Excitation

DSCA43 Devices


Part Number Input RangeOutput RangeBandwidthMechanical FormatIsolation Voltage
-1 to +1 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-2 to +2 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-3 to +3 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-4 to +4 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-5 to +5 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-6 to +6 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-7 to +7 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-8 to +8 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-9 to +9 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-10 to +10 V -10 to +10 V 3 kHz DIN rail 1500 Vrms
-1 to +1 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-1 to +1 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-1 to +1 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-2 to +2 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-2 to +2 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-2 to +2 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-3 to +3 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-3 to +3 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-3 to +3 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-4 to +4 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-4 to +4 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-4 to +4 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-5 to +5 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-5 to +5 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-5 to +5 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-6 to +6 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-6 to +6 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-6 to +6 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-7 to +7 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-7 to +7 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-7 to +7 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-8 to +8 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-8 to +8 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-8 to +8 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-9 to +9 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-9 to +9 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-9 to +9 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms
-10 to +10 V 0 to +10 V 3 kHz DIN rail 1500 Vrms
-10 to +10 V 4 to 20 mA 3 kHz DIN rail 1500 Vrms
-10 to +10 V 0 to 20 mA 3 kHz DIN rail 1500 Vrms

Frequently Asked Questions


Can Dataforth provide calibration reports for modules I purchased?
Yes we can provide calibration reports for the modules that you purchased.

You can either
a) visit https://www.dataforth.com/TestDataReport.aspx to search for Test Report Datasheets by Serial Number or
b) you can send us a list of model numbers and their serial numbers to support@dataforth.com

Does Dataforth have any DSCA modules that can operate on a 12Vdc power supply?
Dataforth does not have any custom modules that run on 12VDC power. Most DSCA modules require a minimum power supply voltage of 15VDC while some require a minimum of 19VDC. Both are suitable for use with nominal 24VDC power supplies over the full operating temperature range of -40C to +85C. Dataforth offers a line of accessory power supplies, PWR-PS5RxW, which have been qualified for use with the DSCA product line. https://www.dataforth.com/catalog/pdf/PWR-PS5RxW.pdf

How do I convert an RMS voltage to its corresponding peak voltage?
To convert an RMS voltage to its corresponding peak voltage, you simply take the RMS voltage value and multiply it by the square root of 2, or roughly 1.414.

For example, 1500Vrms corresponds to a peak voltage of 1500 * 1.414 = 2121 Vp

What is the output resolution of the DSCA series?
The DSCA series is completely analog, so the output resolution cannot be expressed in terms of bits as it is not a digital signal. The only thing that would cause any uncertainty/lack of clarity in your output signal would be the output ripple and noise, which is rated at a typical value of 0.025% span RMS as listed in the datasheet.

Is the calibration of Dataforth modules traceable to NIST standards?
Yes, calibration of Dataforth modules is traceable to NIST standards.

If the input range of my signal conditioner is -1V to +1V and the output range is 0 to 10V, does this mean that it ignores polarity?
A signal conditioner with these I/O ranges does not mean that the module ignores the polarity of your voltage input. The output of voltage input modules are scaled linearly, meaning an input of -1V would correspond to an output of 0V, an input of 0V would correspond to an output of 5V, an input of +1V would correspond to an output of 10V, and so on.

How does the load resistance of a module affect the noise at the output?
Noise at the output of a module is independent of load resistance.

Does Dataforth carry any signal conditioners that interface with AC LVDTs?
Although we do not carry signal conditioners that can interface with AC LVDTs, we do have the SCM5B43, 8B43 and DSCA43 which can interface with DC LVDTs.
Was this content helpful?    Yes / No
Model NumberInput RangeOutput RangeBandwidthSensor TypeStatus*Comments
DSCA43-1448
0V TO 5V0V TO 10V15HZGENERAL PURPOSEPR10V EXC.
DSCA43-1449
0V TO 5V0V TO 10V300HZGENERAL PURPOSEPR10V EXC.
* ... Status Codes: PR = Production, PT = Prototypes, QU = Quoted