DSCL22-01

Loop Powered Isolator - DIN or Panel Mount

DSCL22-01
Loop Powered Isolator - DIN or Panel Mount

Description

Each DSCL22 loop powered isolator provides 1, 2, or 3 channels of analog signal protection by electrically isolating its input from output for any DC process signal in the range of 0-20mA (or 4-20mA). The DSCL22 operates passively, obtaining its power from the transmitted signal.

The input signal is chopped by a proprietary DC chopper circuit, isolation is provided by transformer coupling, a proprietary technique is used to suppress transmission of common mode spikes or surges, and the output signal from the secondary of the transformer is reconstructed to the original input signal.

If one input to two isolated outputs is desired, multiple channel units may be configured as a splitter (see Figure 2).

Specifications

  • Input Range 0 to 20 mA
  • Output Range 0 to 20 mA
  • Mechanical Format DIN rail,Panel Mount
  • Internal Power Supply None
  • Isolation Voltage 4000 Vrms
  • Isolation Type Transformer 1-way
  • Accuracy ±0.05% Span Typical (at 250 Ohm load)
  • Supply Voltage Loop Powered
  • Input Voltage Withstand
  • Gain/Offset Adjust N/A
  • Module Bandwidth 500 Hz
  • NMR (60 Hz) Rejection 20dB / decade above 500Hz
  • External I-to-V Resistor N/A
  • Output Control Continuous
  • Output Resistance
  • Dimensions 4.22 x 3.33 x 0.69 inches
  • Interface Miniature screw terminals
  • Customization no
  • Load Resistance 0 to 1000 Ohms
  • Weight 91 grams (3.21 ounces)

Features

  • No Power Supply Required, Signal Powered from 0-20mA (or 4-20mA) Input
  • Simplified Wiring For Fast Installation
  • DIN Rail or Panel Mountable
  • Narrow DIN Package, Mounts up to 27 Devices into a 19” Rack Space
  • No Recalibration or Maintenance Required
  • Up to 4000Vrms Transformer Isolation
  • Prevents Ground-Loop Problems
  • Prevents the Transfer of Interference Voltages and Currents
  • High Accuracy Over Full Span
  • CE Compliant

Block Diagram

DSCL22 block diagram

Accessories

SCMXRAIL1-1.0
DIN EN 50022-35 x 7.5 (slotted steel), 1 meter length View
SCMXRAIL1-2.0
DIN EN 50022-35 x 7.5 (slotted steel), 2 meter length View
SCMXRAIL2-01
DIN EN 50035-G32 (slotted steel), 1 meter length View
SCMXRAIL2-02
DIN EN 50035-G32 (slotted steel), 2 meter length View
SCMXRAIL3-01
DIN EN 50022-35 x 15 (slotted steel), 1 meter length View
SCMXRAIL3-02
DIN EN 50022-35 x 15 (slotted steel), 2 meter length View

Competitive Cross-Reference

  • No cross reference is available.
View Dataforth cross-reference data.
The information available through this competitive cross reference guide are based upon product catalog information obtained from a variety of sources. The competitive cross reference information is being provided to you free of charge for your use. While Dataforth Corp has used reasonable efforts to ensure data accuracy, Dataforth Corp does not guarantee that it is error-free, nor does Dataforth Corp make any other representation, warranty or guarantee that the information is accurate, correct, reliable or up-to-date. Dataforth Corp expressly disclaims all implied warranties regarding this information, including but not limited to any implied warranties of merchantability or fitness for a particular purpose.

This information is provided only as a convenience on an "as is" basis and Dataforth Corp. or its representatives or distributors are not responsible for any incorrect, inaccurate, or incomplete information. You are solely responsible for (1) selecting the appropriate Dataforth products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable standards, and any other safety, security, or other requirements.

FAQ

Due to resource constraints on my computer, I'm unable to open the three dimensional CAD models provided on your website. Does Dataforth provide two demensional CAD models for download as well?
Two dimensional CAD models can be generated upon customer request. Please contact Customer Service for assistance.
How does the load resistance of a module affect the noise at the output?
Noise at the output of a module is independent of load resistance.
Can Dataforth provide calibration reports for modules I purchased?
Yes we can provide calibration reports for the modules that you purchased. You can either a) visit https://www.dataforth.com/TestDataReport.aspx to search for Test Report Datasheets by Serial Number or b) you can send us a list of model numbers and their serial numbers to support@dataforth.com
Does Dataforth have an isolator with one input featuring two or more outputs?
No, but this function can be implemented with a two or three channel loop isolator, such as DSCL22-11, DSCL22-21, DSCL24-11, or DSLC24-12. Connect all inputs in series with each other. Sum together all input burden voltages so as not to exceed the maximum loop voltage available.

Keywords/Phrases: DSCL, DSCL one input multi-output loop isolator, one input multi-output loop isolator
Does Dataforth have a 4-channel 4-20mA isolator?
No. However, Dataforth does have two and three-channel 4-20mA isolators as shown in the following table.

Model Description
DSCL22-11 2-channel 4-20mA isolator
DSCL22-21 3-channel 4-20mA isolator
DSCL23-02 2-channel 4-20mA Isolator with DC Supply for 2-wire transmitter
DSCL24-11 2-channel 4-20mA isolator

Keywords/Phrases: 4-20mA isolator, 4-channel 4-20mA isolator, 4-channel 4-20mA DIN mount isolator

Was this content helpful?
Thank you for your feedback!
Menu