DSCP62: Thermocouple-to-DC Current/Voltage Converter with Relay Output

DSCP62
Thermocouple-to-DC Current/Voltage Converter with Relay Output

Product Availability:

Description

Each DSCP62 Thermocouple Converter provides a single channel of thermocouple input which is amplified, linearized and converted to a high-level current or voltage output. Thermocouple type, measurement range, filter, output type and range, and fault indication may be configured by dip-switch. An auxiliary relay output is provided to generate an alarm or act as a thermostat. Power can be applied directly to the converter’s terminals or through a DIN rail mounted bus connector accessory, eliminating the need to wire power to each individual converter.

Features

  • Input: Thermocouple types J, K, E, N, S, R, B, T
  • Output Current: 0 to 20, 4 to 20, 20 to 0, 20 to 4mA
  • Output Voltage: 0 to 5, 1 to 5, 0 to 10, 10 to 0VDC
  • Auxiliary Relay for Alarm or Control
  • 1500Vrms Galvanic Isolation, 3-Way
  • 19.2 to 30VDC Power
  • Spring Cage Clamp Connection
  • 14-Bit Resolution
  • Better than ±0.1% Accuracy
  • Configuration by Dip-Switch
  • Compact 6.2mm DIN Housing
  • CE Compliant

Block Diagram

FAQ

Frequently Asked Questions


Can Dataforth provide calibration reports for modules I purchased?
Yes we can provide calibration reports for the modules that you purchased.

You can either
a) visit https://www.dataforth.com/TestDataReport.aspx to search for Test Report Datasheets by Serial Number or
b) you can send us a list of model numbers and their serial numbers to support@dataforth.com

Can terminals 6 & 8 on DSCP62 be connected together without damaging the unit?
Yes. However, keep in mind, when those terminals are not connected together, the module offers up to 1500Vrms isolation of the output section from the power section.
When those terminals are connected together, that isolation is cancelled, so the input of the device the module output is driving can no longer float.

Module still retains 1500Vrms withstand capability to the T/C or other type of input when pin 6 and 8 are tied together.



How does the load resistance of a module affect the noise at the output?
Noise at the output of a module is independent of load resistance.
Was this content helpful?    Yes / No

Competitive Cross-Reference

  • No cross reference is available.
View Dataforth cross-reference data.
The information available through this competitive cross reference guide are based upon product catalog information obtained from a variety of sources. The competitive cross reference information is being provided to you free of charge for your use. While Dataforth Corp has used reasonable efforts to ensure data accuracy, Dataforth Corp does not guarantee that it is error-free, nor does Dataforth Corp make any other representation, warranty or guarantee that the information is accurate, correct, reliable or up-to-date. Dataforth Corp expressly disclaims all implied warranties regarding this information, including but not limited to any implied warranties of merchantability or fitness for a particular purpose.

This information is provided only as a convenience on an "as is" basis and Dataforth Corp. or its representatives or distributors are not responsible for any incorrect, inaccurate, or incomplete information. You are solely responsible for (1) selecting the appropriate Dataforth products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable standards, and any other safety, security, or other requirements.

Price shown is for small quantities. For large quantities, add to cart and submit an RFQ.