DSCL23
4-20mA Isolator with DC Supply - DIN or Panel Mount
                    Each DSCL23 loop powered isolator provides 1 or 2 channels of analog signal protection by electrically isolating its input from output for any DC process signal in the range 4-20mA. The DSCL23 feeds isolated DC power to the field transmitter and returns a fully isolated 4-20mA analog signal.
The input signal is chopped by a proprietary DC chopper circuit, isolation is provided by transformer coupling, a proprietary technique is used to suppress transmission of common mode spikes or surges, and the output signal from the secondary of the transformer is reconstructed to the original input signal.
                The input signal is chopped by a proprietary DC chopper circuit, isolation is provided by transformer coupling, a proprietary technique is used to suppress transmission of common mode spikes or surges, and the output signal from the secondary of the transformer is reconstructed to the original input signal.
Certifications
Documents
Product Availability
                            Usually stock to 3-5 weeks. Contact Customer Service for current lead times.
                        
                        
                    Features
- Feeds DC Power to 4 to 20mA Transmitter, Isolates Loop
- Simplified Wiring for Quick Install and Signal Protection
- DIN Rail or Panel Mountable
- Narrow DIN Package, Mounts up to 27 Devices into a 19" Rack Space
- No Recalibration or Maintenance Required
- 2300Vrms Transformer Isolation
- Prevents Ground-Loop Problems
- Prevents the Transfer of Interference Voltages and Currents
- High Accuracy Over Full Span
- CE Compliant
Block Diagram
 
            Ordering
            
    NOTE: Data in below table can be filtered. Please use the
    
    to make your selection. If you have any questions about the displayed data, 
    please contact Customer Service at +1 520-741-1404 or sales@dataforth.com
    FAQ
        Due to resource constraints on my computer, I'm unable to open the three dimensional CAD models provided on your website.  Does Dataforth provide two demensional CAD models for download as well?
    
    
        Two dimensional CAD models can be generated upon customer request.  Please contact Customer Service for assistance.
    
    
        How does the load resistance of a module affect the noise at the output?
    
    
        Noise at the output of a module is independent of load resistance.
    
    
        Can Dataforth provide calibration reports for modules I purchased?
    
    
        Yes we can provide calibration reports for the modules that you purchased.
You can either
a) visit https://www.dataforth.com/TestDataReport.aspx to search for Test Report Datasheets by Serial Number or 
b) you can send us a list of model numbers and their serial numbers to support@dataforth.com
    
    
        Why do I see a -10V shift when I change to a DSCL23 from a DSCA42-01C or similar? 
    
    
        The DSCA42-01C internal electronics is powered by an overall power supply and then the module output circuitry provides the output current whose return side (or negative side) is connected internally to the power supply common. This causes the output signal to be positive with respect to the common. 
Whereas, the DSCL23 is loop-powered through its output terminals. That puts the 4-20mA receiver (the load) in series with the power supply. So when you measure the voltage from the power supply common (- terminal) to the other side of the load you will see a negative signal. The module could be made usable if the power supply has a fully floating output and you can make terminal 1 (the return current terminal) the common and measure the positive signal across the load from the power supply (-) to terminal 1 (the return current terminal), the common.
A better match for your application is the DSCA42-01C. Its internal electronics is powered by an overall power supply and then the module output circuitry provides the output current whose return side (or negative side) can be connected to the power supply common. This causes the output signal to be positive with respect to the common.
Keywords/Phrases: 4-20mA isolator with loop power, 2-wire transmitter interface signal conditioner with loop power
    
    Whereas, the DSCL23 is loop-powered through its output terminals. That puts the 4-20mA receiver (the load) in series with the power supply. So when you measure the voltage from the power supply common (- terminal) to the other side of the load you will see a negative signal. The module could be made usable if the power supply has a fully floating output and you can make terminal 1 (the return current terminal) the common and measure the positive signal across the load from the power supply (-) to terminal 1 (the return current terminal), the common.
A better match for your application is the DSCA42-01C. Its internal electronics is powered by an overall power supply and then the module output circuitry provides the output current whose return side (or negative side) can be connected to the power supply common. This causes the output signal to be positive with respect to the common.
Keywords/Phrases: 4-20mA isolator with loop power, 2-wire transmitter interface signal conditioner with loop power
        Does Dataforth have a 4-channel 4-20mA isolator? 
    
    
        No. However, Dataforth does have two and three-channel 4-20mA isolators as shown in the following table. 
Model Description
DSCL22-11 2-channel 4-20mA isolator
DSCL22-21 3-channel 4-20mA isolator
DSCL23-02 2-channel 4-20mA Isolator with DC Supply for 2-wire transmitter
DSCL24-11 2-channel 4-20mA isolator
Keywords/Phrases: 4-20mA isolator, 4-channel 4-20mA isolator, 4-channel 4-20mA DIN mount isolator
    
                
            Model Description
DSCL22-11 2-channel 4-20mA isolator
DSCL22-21 3-channel 4-20mA isolator
DSCL23-02 2-channel 4-20mA Isolator with DC Supply for 2-wire transmitter
DSCL24-11 2-channel 4-20mA isolator
Keywords/Phrases: 4-20mA isolator, 4-channel 4-20mA isolator, 4-channel 4-20mA DIN mount isolator
Custom Modules
    Below is a list of existing custom modules. If you don't see a module matching your target specifications, contact Customer Service and Application Support to discuss design guidelines and
    design feasibility. Customer Service and Application Support can be reached at
    sales@dataforth.com or +1-800-444-7644.
    NOTE: Data in below table can be filtered. Please use the
    
    to make your selection. If you have any questions about the displayed data, 
    please contact Customer Service at +1 520-741-1404 or sales@dataforth.com
    * ... Status Codes: PR = Production, PT = Prototypes, QU = Quoted
            
        We want your feedback!
We are interested in your feedback regarding our products. Please let us know what you think and if you have any questions regarding the SCM5B32 and how this product could apply to your application. Your feedback is very valuable to us and very much appreciated.
            
            Was this content helpful?
        
        
        Thank you for your feedback!
    
 
         
             Signal Conditioning
 Signal Conditioning
                
 Data Acquisition & Control
                    Data Acquisition & Control
                
 4-20mA Transmitters
                    4-20mA Transmitters
                
 IoT Power & Energy Monitoring
                    IoT Power & Energy Monitoring
                
 Data Communications
                    Data Communications
                
 Power Supplies
                    Power Supplies
                 Software
                    Software
                